    9.2° FLOOR – CONFERENCE ROOM
    9.1 CALCULATIONS REVIEW
    The lighting review shows higher lighting levels than the Dragon International design,as
    indicated in the premises.
    In this case the values are too higher (three times higher) so it is reasonable to think that there
    was some dimming percentage or some changes in lamps,due to specific design criteria,not
    indicated in the available documentation.
    The medium lighting level on the working surface (Em) is:1274 Lx in the Telmotor review
    and 395 Lx in Dragon International design.
    The Telmotor review uses the same lighting fixtures of the Dragon International design,with
    the same accessories,same quantities and the same photometric data with the exception of the
    fixtures inside the cave of the ceiling for what it was impossible to find the photometric data
    for Dialux,the review was done with OSRAM fixtures with same photometric data as
    indicated in the data sheet included in the Dragon International design.
    In the Dragon International design,in some ERCO fixtures,the luminous flux was manually
    modified,indeed the 22463010 model has 50W lamps with 36° reflector.The original
    photometric data given by ERCO shows a flux value of 1200 Lm instead of the one inserted
    in Dragon International design that is 900 Lm.
    As indicated in the premises,this can be for less efficient lamps or for a dimming percentage
    manually inserted in the calculation.
    The Dragon International design and the Telmotor review consider part of the conference
    room.
    In the drawings available the central squares on the ceiling are 110cm wide,the 28W lamps
    employed are 114,4cm; seems to be a design error that can be correct with a change of lamps
    power at 21W with the same lamps model.In this case the lamps dimension is 84,9cm.
    英語人氣:717 ℃時間:2020-06-11 01:59:28
    優(yōu)質解答
    9 .2 °地板-會議室
    9.1計算綜述
    燈光照明審查表明較高水平比龍國際設計,
    中所表明的處所.
    在這種情況下,價值觀念也較高( 3倍) ,這樣可以合理地認為,
    有些調(diào)光百分比或一些變化燈,由于具體的設計標準,而不是
    表明在現(xiàn)有的文件.
    中期照明水平的工作表面群( EM )是:1274年光照在Telmotor審查
    和395勒克斯在龍國際設計.
    審查的Telmotor使用同樣的燈具龍國際設計,
    同樣的配件,同樣的數(shù)量和相同的光度數(shù)據(jù)除
    洞穴內(nèi)的固定裝置的上限是什么不可能找到的光度數(shù)據(jù)
    為Dialux ,審查是與歐司朗燈具同光度數(shù)據(jù)
    中所表明的數(shù)據(jù)包括在龍國際設計.
    在龍國際設計,在一些ERCO裝置,該光通量是手動
    修改,確實22463010模型50瓦燈泡的36 °反射.原來
    光度數(shù)據(jù)所給予ERCO顯示通量價值1200流明,而不是一個插入
    在龍國際設計,900流明.
    如房地,這可能是效率較低的燈或調(diào)光的百分比
    手動插入計算.
    龍的國際設計和Telmotor審查的一部分,審議會議
    房間.
    在提供圖紙的中央廣場上的最高限額是一百一十厘米寬,28W燈
    就業(yè)是114,4厘米;似乎是一個設計錯誤,可以正確的變動燈
    功率21W的相同燈模式.在這種情況下,燈層面84,9厘米.